All cut sheets
Download PDF
MESH by VT Wireless Energy Management
VT Engineering Inc.
[email protected] · 604-771-5543
mesh.vteng.ca
Mesh Leaf enclosure, silver galvanized, isometric view Made in Canada

Mesh Leaf

Wireless load-management leaf node · one per managed stall

The Mesh Leaf installs between the unit breaker panel and the managed load — typically a Level 2 EV charger today, with heat pumps and other flexible loads on roadmap. It monitors the local feeder, receives current limits by mesh radio from the upstream Mesh Core, and enforces them locally so total building load stays inside the approved envelope. The resident's equipment operates normally.

Fail-safe by design
Throttles to a safe current if radio drops.
No internet required
Local mesh radio to the Core — no Wi-Fi or cellular.
Flexible-load ready
EV chargers today; heat pumps and other loads next.
System architecture
Meter
1
Building service

Reads total electrical demand on the service feeders.

Balance
2
Mesh Core

Calculates a safe load budget for the building.

Enforce
3
Mesh Leaf

Applies the budget locally at each managed stall.

Operate
4
Managed load

EV chargers today; heat pumps & more on roadmap.

Key features
Monitors 120/240 V or 120/208 V at the unit panel
Two 200 A split-core CTs included, 6.0 m leads
Long-range mesh radio to the upstream Mesh Core
Supports up to 50 A load circuits, 208/240 V
Surface or recess mount, knock-outs on every face
3φ CT option available for multi-phase service
Compact 10″ × 8″ × 4″ steel enclosure
CSA SPE-1000 approved · designed and built in BC
Specifications
System
EVEMS leaf node · multi-load capable
Feeder voltage
120/240 V or 120/208 V, 1φ (3φ CT option)
Current sensors
Two 200 A split-core CTs, 6.0 m leads
Load feed
208 V or 240 V hardwired, max 50 A circuit
Safety threshold
Throttles on Core command when a point exceeds 80%
Comms
Long-range mesh radio — no internet required
Enclosure
10"H × 8"W × 4"D, knock-outs on every face
Mounting
Surface or recess at the unit panel
Certifications
CSA SPE-1000 · Technical Safety BC
Origin
Designed and manufactured in Canada
What you can count on
Fail-safe by design

If radio communication with the Core is lost, the Leaf falls back to a conservative configured current — never an unmanaged full-rate draw. CT readings are verified locally before the downstream load circuit is released.

You own the hardware

No monthly fees. No per-charge fees. No subscription contracts. 2-year parts & labour warranty, extended options available.

Designed and built in BC · Compliant with
CSA Group
SPE-1000 EV infrastructure
Technical Safety BC
Electrical safety authority
WorkSafeBC
OHS-compliant installs
Engineers and Geoscientists BC
Member firm
BC Hydro Alliance Member
Utility partner